Pluggable communication module with different solutions
The DDZY876 is used for a wide range of smart prepaid metering applications.
Option for communication module supports both GPRS+PLC(G3) communication. When one communication method experiences poor performance, it automatically switches to the other, ensuring highly reliable two-way communication with the AMI system.
The auxiliary terminals support RS485, RS232, RJ45, and MBUS, etc.
DLMS/COSEM standard compliant.
IEC62056-21 compliant optical port &VTC allowing for easy data interrogation.
Operate in both prepayment and postpayment.
Measurement of electrical parameters (Active power, reactive power, current, voltage, maximum demand, etc.)
Programmable load limit and low credit warning.
Detection and record event such as cover opening and terminal cover opening, current reverse, bypass, etc.
Downlink communication MBUS, uplink communication GPRS+G3 PLC.
Digits: 6 integers + 2 decimal.
ITEMS | PARAMETERS |
Nominal voltage (Un) | 230V |
Limited voltage | 60%~130%Un |
Nominal frequency (Fn) | 50Hz/60Hz |
Basic current (Ib) | 5A |
Maximum current (Imax) | 100A |
Starting current (Ist) | 5mA |
Active energy constant | 1000 imp/kWh, 1000 imp/kvarh |
Measurement Accuracy | Class 0.5S for active and reactive |
Voltage circuit burden | <0.5W, <1VA |
Current circuit burden | <0.2VA |
Operation Temperature | -25℃ to +70℃ |
Storage Temperature | -40℃ to +85℃ |
Insulation level | 4kV rms 1min |
Voltage impulse withstand | 6kV 1.2/50 μs |
Insulation System Classification | Class II |
Contact discharge | 8kV |
Air discharge | 15kV |
27MHz to 500MHz typical | 10V/m |
100kHz to 1GHz typical |
|
Fast transient burst test | 4kV |
Meter shell Protection Rate | IP54 |
Maximum cable size | 4-35 mm2 |
Connection diagram | PNNP / PPNN |